Backflow prevention for businesses

If your property connects to our water or recycled water pipes, you must install the right backflow containment device.

On this page

What is backflow?

Backflow occurs when used water from a customer's property flows backward into our pipes. It may carry contaminants like chemicals, oil, bacteria, mud and debris that can harm people's health. Contaminated water can pose serious risks.

Preventing backflow is important to protect our water quality and people's health.


How backflow occurs

Backflow is more likely to occur:

  • if there's a drop in pressure in the main, for example, during a water main break
  • if water pressure at the property is higher than at the main, such as if a pump is operating on the site.

Contaminants may enter the drinking water system through a cross connection caused by:

  • faulty plumbing
  • hoses submerged in buckets, tanks or pools.

Cross connections are unauthorised plumbing connections between 2 water sources that should be separate, such as a drinking water system and a recycled water or wastewater system.


What backflow devices are

Backflow prevention containment devices stop potentially contaminated water flowing back into our water supply system. They use one or more of the following features to stop water flowing backward:

  • a valve that only lets water go in one direction
  • an air gap
  • a break tank.

What you must do

You must have the correct backflow prevention device installed and keep it in good working order.

You must hire an accredited backflow plumber to:

  • assess your site’s hazard rating
  • install, test and register the device
  • test the device every year
  • send us the results within 2 days.

Backflow prevention must comply with the Plumbing Code of Australia.

Owners of low hazard properties with meters larger than 25 mm must get a non-testable backflow prevention containment device installed. Our 20 mm and 25 mm meters have an integral backflow prevention device built in. These are suitable for low hazard connections.

Owners of medium hazard properties must install an approved testable backflow prevention device that meets the requirements for their property. 

Common examples include:

  • testable double check valves (DCVs) for drinking water connections
  • double check detector assemblies (DCDAs) for fire service connections.

Owners of high hazard properties must install an approved backflow prevention device that meets the requirements for their property.

Common examples of backflow prevention devices used for high hazard properties include:

  • reduced pressure zone devices (RPZDs)
  • registered air gaps
  • registered break tanks.

If we've given you permission to use a metered standpipe on our pipes, your standpipe must have a testable double check valve incorporated into its design.

You need a backflow prevention device on water main connections you use for construction and renovation. If you're building more than a single standalone house, we consider it to be a high backflow hazard.

  • If your property has a sprinkler or fire hydrant service, it must have a testable double check detector assembly on each connection. The double check detector assemblies must be installed close to where the water service enters your property and upstream of any booster assembly or off-take from the fire service. You must not use galvanised pipes and fittings on the upstream side of the connection.
  • If your property has a window or wall drencher system, you must install a non-testable low hazard device.

If you don't know your site's hazard rating or don't get it assessed, we'll assume it's a high hazard. Owners of properties with unknown hazard ratings must get a registered break tank, reduced pressure zone device or registered air gap installed.


Who can install and test your device

You must use licensed plumbers and accredited backflow plumbers.

  • A licensed plumber can install your device.
  • An accredited backflow plumber can test and register your device with us and confirm it is operating correctly.

Some plumbers are qualified to both install and test backflow prevention devices.

To find an accredited backflow plumber near you, use our backflow plumber search.


What we will do

We keep a register of all installed testable backflow prevention containment devices, and will remind you when it's time to get your backflow device tested each year.

We audit a sample of installations to make sure they comply with Australian Standards AS/NZS 3500:1 and AS/NZS 2845, and our connection requirements.

If you don't comply with our backflow requirements or notices, we could:

  • test the device and charge you for the service
  • restrict your water supply
  • disconnect you
  • charge you any costs we incur to make your connection satisfy our requirements.

If your installation doesn't comply with the standards, we'll send a notice asking you to repair, maintain, test or replace the device.