WORONORA WATER FILTRATION PLANT
1 April 2004 to 30 June 2004

Raw Water

Filtered Water

No. of samples

Min

Ave

Max

No. of samples

Min

Ave

Max

Guideline Value*

Samples passed

MICROBIOLOGICAL

total coliforms***

13

4

-

490

13

0

-

3

0 Orgs/100 mL

92.3%

E. coli

13

0

-

16

13

0

-

0

0 Orgs/100 mL

100%

Giardia

13

0

-

0

#

#

-

#

**

NA

Cryptosporidium

13

0

-

0

#

#

-

#

**

NA

PHYSICAL/CHEMICAL

turbidity

13

0.57

0.86

1.43

13

0.06

0.09

0.14

<5 NTU

100%

true colour

13

4

6

11

13

<2

<2

3

<15 HU

100%

pH

13

6.6

6.9

7.5

13

7.6

7.8

8.0

6.5 - 8.5 pH units

100%

free chlorine

#

#

#

#

13

0.00

0.00

0.00

<5 mg/L

100%

monochloramine

#

#

#

#

13

1.56

1.70

1.78

<3 mg/L

100%

fluoride

#

#

#

#

13

1.00

1.05

1.11

<1.5 mg/L

100%

trihalomethanes

#

#

#

#

3

0.024

0.028

0.034

<0.25 mg/L

100%

iron

13

0.081

0.097

0.121

13

<0.010

<0.010

0.013

<0.3 mg/L

100%

aluminium

13

0.030

0.061

0.108

13

0.019

0.024

0.031

<0.2 mg/L

100%

manganese

13

0.007

0.009

0.012

13

<0.001

0.001

0.001

<0.1 mg/L

100%


All parameters complied with the guidelines during the quarter for the water leaving the water filtration plant. However, Total coliforms were detected in 1 out of a total of 13 samples collected during the quarter.

The Australian Drinking Water Guidelines for 1996 recognise that occasionally there will be test results above the Guidelines values. The Guidelines do not require a 100% result in all cases. Each positive test result is investigated and long-term actions are taken to minimise the risk of them happening again.

There is no requirement to sample free chlorine or monochloramine, fluoride and trihalomethanes in the raw water.

* Australian Drinking Water Guidelines, NH&MRC 1996, normally reported on an annual basis. This represents a quarterly result only.

** No guideline set for raw water

# Not required

Raw water is defined as the water entering the Water Filtration Plant from the dam
Filtered Water is defined as the water leaving the Water Filtration Plant

 


ANNUAL

WORONORA WATER FILTRATION PLANT
1 July 2003 to 30 June 2004

Raw Water

Filtered Water

No. of samples

Min

Ave

Max

No. of samples

Min

Ave

Max

Guideline Value*

Samples passed

MICROBIOLOGICAL

total coliforms***

48

1

-

490

53

0

-

3

0 CFU/100 mL

98.1%

E. coli***

48

0

-

16

53

0

-

0

0 CFU/100 mL

100%

Giardia

52

0

-

0

#

#

-

#

**

NA

Cryptosporidium

52

0

-

0

#

#

-

#

**

NA

PHYSICAL/CHEMICAL

turbidity

48

0.50

0.96

7.49

53

0.06

0.12

0.25

<5 NTU

100%

true colour

48

<2

5

11

53

<2

<2

3

<15 HU

100%

pH

48

6.4

7.0

7.8

53

7.5

7.8

8.0

6.5 - 8.5 pH units

100%

free chlorine

#

#

#

#

53

0.00

0.01

0.12

<5 mg/L

100%

monochloramine

#

#

#

#

53

1.35

1.64

1.94

<3 mg/L

100%

fluoride

#

#

#

#

53

0.88

1.04

1.25

<1.5 mg/L

100%

trihalomethanes

#

#

#

#

12

0.023

0.033

0.046

<0.25 mg/L

100%

iron

48

0.047

0.088

0.155

53

<0.010

0.011

0.089

<0.3 mg/L

100%

aluminium

48

0.017

0.056

0.136

53

0.016

0.032

0.068

<0.2 mg/L

100%

manganese

48

0.004

0.008

0.014

53

<0.001

0.002

0.032

<0.1 mg/L

100%

* Australian Drinking Water Guidelines, NH&MRC 1996, normally reported on an annual basis.

** No guideline set for raw water

# Not required

Raw water is defined as the water entering the Water Filtration Plant from the dam
Filtered Water is defined as the water leaving the Water Filtration Plant