SW_Logo  

Overview

Summary

Where does my water come from?

What is the quality of my water?

Water Quality Data

Water Quantity Data

Literature Review

Catchment Issues

Glossary

Frequently Asked Questions

Community Language Information

 

-> Quarterly Water Quality Reports -> Fourth Quarter 2003/2004 -> Water Quality Data

Quarterly Results
Annual Results

QUARTERLY

ILLAWARRA WATER FILTRATION PLANT
1 April 2004 to 30 June 2004

Raw Water

Filtered Water

No. of samples

Min

Ave

Max

No. of samples

Min

Ave

Max

Guideline Value*

Samples passed

MICROBIOLOGICAL

total coliforms***

13

95

-

517

13

0

-

0

0 Orgs/100 mL

100%

E. coli

13

0

-

35

13

0

-

0

0 Orgs/100 mL

100%

Giardia

13

0

-

0

1

0

-

0

**

NA

Cryptosporidium

13

0

-

0

1

0

-

0

**

NA

PHYSICAL/CHEMICAL

turbidity

13

0.60

0.89

1.48

13

0.07

0.10

0.13

<5 NTU

100%

true colour

13

3

4

6

13

<2

<2

3

<15 HU

100%

pH

13

7.1

7.4

7.8

13

7.6

7.7

7.8

6.5 - 8.5 pH units

100%

free chlorine

#

#

#

#

13

1.15

1.30

1.52

<5 mg/L

100%

mono chloramine

#

#

#

#

13

0.05

0.07

0.09

<3 mg/L

100%

fluoride

#

#

#

#

13

0.96

1.01

1.05

<1.5 mg/L

100%

trihalomethanes

#

#

#

#

3

0.039

0.047

0.053

<0.25 mg/L

100%

iron

13

0.039

0.076

0.197

13

<0.010

0.012

0.026

<0.3 mg/L

100%

aluminium

13

<0.010

<0.010

0.016

13

<0.010

0.014

0.020

<0.2 mg/L

100%

manganese

13

0.013

0.016

0.020

13

<0.001

0.002

0.014

<0.1 mg/L

100%


All parameters complied with the relevant standards during the quarter for the water leaving the water filtration plant.

There is no requirement to sample free chlorine or monochloramine, fluoride and trihalomethanes in the raw water.

* Australian Drinking Water Guidelines, NH&MRC 1996, normally reported on an annual basis. This represents a quarterly result only.

** No guideline set for raw water

# Not required

Raw water is defined as the water entering the Water Filtration Plant from the dam
Filtered Water is defined as the water leaving the Water Filtration Plant

 


ANNUAL

ILLAWARRA WATER FILTRATION PLANT
1 July 2003 to 30 June 2004

Raw Water

Filtered Water

No. of samples

Min

Ave

Max

No. of samples

Min

Ave

Max

Guideline Value*

Samples passed

MICROBIOLOGICAL

total coliforms***

53

36

-

5500

53

0

-

0

0 CFU/100 mL

100%

E. coli***

53

0

-

35

53

0

-

0

0 CFU/100 mL

100%

Giardia

53

0

-

0

1

0

-

0

**

NA

Cryptosporidium

53

0

-

0

1

0

-

0

**

NA

PHYSICAL/CHEMICAL

turbidity

53

0.60

0.97

1.95

53

0.07

0.13

0.21

<5 NTU

100%

true colour

53

<2

4

6

53

<2

<2

3

<15 HU

100%

pH

53

7.0

7.3

7.8

53

7.2

7.7

8.0

6.5 - 8.5 pH units

100%

free chlorine

#

#

#

#

53

1.10

1.26

1.52

<5 mg/L

100%

mono chloramine

#

#

#

#

53

0.02

0.06

0.09

<3 mg/L

100%

fluoride

#

#

#

#

53

0.95

1.00

1.05

<1.5 mg/L

100%

trihalomethanes

#

#

#

#

12

0.039

0.046

0.053

<0.25 mg/L

100%

iron

53

0.031

0.086

0.197

53

<0.010

0.012

0.027

<0.3 mg/L

100%

aluminium

53

<0.010

0.010

0.030

53

<0.010

0.020

0.040

<0.2 mg/L

100%

manganese

53

0.005

0.014

0.034

53

<0.001

0.001

0.014

<0.1 mg/L

100%

* Australian Drinking Water Guidelines, NH&MRC 1996, normally reported on an annual basis.

** No guideline set for raw water

# Not required

Raw water is defined as the water entering the Water Filtration Plant from the dam
Filtered Water is defined as the water leaving the Water Filtration Plant