SW_Logo  

Overview

Summary

Where does my water come from?

What is the quality of my water?

Water Quality Data

Water Quantity Data

Literature Review

Catchment Issues

Glossary

Frequently Asked Questions

Community Language Information

 

-> Quarterly Water Quality Reports -> Fourth Quarter 2003/2004 -> Water Quality Data

Quarterly Results
Annual Results

QUARTERLY

GREAVES CREEK WATER FILTRATION PLANT
1 April 2004 to 30 June 2004

Raw Water

Filtered Water

No. of samples

Min

Ave

Max

No. of samples

Min

Ave

Max

Guideline Value*

Samples passed

MICROBIOLOGICAL

total coliforms***

12

150

-

1100

12

0

-

0

0 Orgs/100 mL

100%

E. coli

12

0

-

15

12

0

-

0

0 Orgs/100 mL

100%

Giardia

13

0

-

0

#

#

-

#

**

NA

Cryptosporidium

13

0

-

0

#

#

-

#

**

NA

PHYSICAL/CHEMICAL

turbidity

12

1.19

1.36

1.8

12

0.07

0.29

0.91

<5 NTU

100%

true colour

12

7

8

10

12

<2

<2

3

<15 HU

100%

pH

12

6.3

7.1

8

12

7.2

7.6

7.8

6.5 - 8.5 pH units

100%

free chlorine

#

#

#

#

12

0.70

0.80

0.98

<5 mg/L

100%

monochloramine

#

#

#

#

12

0.00

0.06

0.10

<3 mg/L

100%

fluoride

#

#

#

#

12

0.97

1.08

1.16

<1.5 mg/L

100%

trihalomethanes

#

#

#

#

3

0.028

0.037

0.041

<0.25 mg/L

100%

iron

12

0.188

0.330

0.493

12

<0.010

0.019

0.071

<0.3 mg/L

100%

aluminium

12

0.033

0.046

0.062

12

0.014

0.025

0.042

<0.2 mg/L

100%

manganese

12

0.013

0.021

0.034

12

0.001

0.006

0.033

<0.1 mg/L

100%


All parameters complied with the guidelines during the quarter for the water leaving the water filtration plant.

There is no requirement to sample free chlorine or monochloramine, fluoride and trihalomethanes in the raw water.

* Australian Drinking Water Guidelines, NH&MRC 1996, normally reported on an annual basis. This represents a quarterly result only.

** No guideline set for raw water

# Not required

Raw water is defined as the water entering the Water Filtration Plant from the dam
Filtered Water is defined as the water leaving the Water Filtration Plant

 


ANNUAL

GREAVES CREEK WATER FILTRATION PLANT
1 July 2003 to 30 June 2004

Raw Water

Filtered Water

No. of samples

Min

Ave

Max

No. of samples

Min

Ave

Max

Guideline Value*

Samples passed

MICROBIOLOGICAL

total coliforms***

52

71

-

>2400

52

0

-

2

0 CFU/100 mL

98.1%

E. coli***

52

0

-

80

52

0

-

0

0 CFU/100 mL

100%

Giardia

52

0

-

0

#

#

-

#

**

NA

Cryptosporidium

52

0

-

0

#

#

-

#

**

NA

PHYSICAL/CHEMICAL

turbidity

52

0.41

1.46

3.99

52

0.07

0.25

0.91

<5 NTU

100%

true colour

52

6

10

16

52

<2

<2

3

<15 HU

100%

pH

52

6.3

6.9

8.0

52

7.2

7.5

7.8

6.5 - 8.5 pH units

100%

free chlorine

#

#

#

#

52

0.46

0.79

1.05

<5 mg/L

100%

monochloramine

#

#

#

#

52

0.00

0.05

0.16

<3 mg/L

100%

fluoride

#

#

#

#

52

0.97

1.06

1.16

<1.5 mg/L

100%

trihalomethanes

#

#

#

#

12

0.028

0.044

0.060

<0.25 mg/L

100%

iron

52

0.188

0.288

0.493

52

<0.010

0.021

0.071

<0.3 mg/L

100%

aluminium

52

0.033

0.093

0.214

52

0.014

0.030

0.048

<0.2 mg/L

100%

manganese

52

0.013

0.023

0.048

52

0.001

0.007

0.033

<0.1 mg/L

100%

* Australian Drinking Water Guidelines, NH&MRC 1996, normally reported on an annual basis.

** No guideline set for raw water

# Not required

Raw water is defined as the water entering the Water Filtration Plant from the dam
Filtered Water is defined as the water leaving the Water Filtration Plant